|
Building Code

Disclaimer
This web
site has a number of downloads available in the
Adobe Acrobat Reader (PDF) format. Click on the logo below to download the Reader software directly from the Acrobat website.

|
(Click
here to view an Adobe Acrobat Reader version of this document.)
-
The
National Electrical Code 1999 edition have been adopted by Will County
and apply to all electrical installations as though fully written and
set forth herein, except as specifically noted otherwise in this code.
-
LICENSE:
All Electrical contractors engaged in the performance of electrical work
shall be licensed per the Illinois Municipal Code 11-33-1. The
contractor shall file with the Will County Building Department a copy of
the valid license and said license shall reflect the scope of the work.
-
PERMITS:
Permits are required for all electrical work. Permits for electrical
work shall be issued only when a duly licensed and bonded electrical
contractor is listed on the permit application. It shall be unlawful for
any person to install, alter, or repair any electrical wire or apparatus
by authority of the permit issued to and the use of some other person.
EXCEPTION:
Qualified homeowners who can demonstrate their ability to perform such
work, to the satisfaction of the Building Department, may do work on
their own place of residence.
In
all cases, except single family dwellings, before any electrical service
receives a permit an electrical license must be on file with the Will
County Building Department.
-
It
shall be unlawful for any person to alter, disturb or change any
electrical wiring or equipment or to permit any electrical wiring or
equipment to be altered, disturbed, or changed unless done in
conformity with the regulations in this code.
-
Where
rework or rewiring of any building or structure is 50% or more, then
all wiring in the entire structure shall be installed as per the
currently adopted code.
-
All
electrical wiring shall be copper.
-
It
is the express intent of this code that NEC Articles 320, 324, 328,
331, 333,334, 336, 338, and 339 NOT be adopted.
-
Electrical
metallic tubing (thin wall) shall not be installed underground or in
concrete that is in contact with the earth.
-
All
electrical services shall be rigid metal conduit, or intermediate
metal conduit.
-
No
more then 10' of service entrance conductor shall be allowed or
protected means of disconnect.
-
If
required by the authority having jurisdiction a diagram showing
service and feeders wire sizes, type of conductors, calculated loads,
the area in square feet being supplied, and demand factors shall be
supplied. Also panel schedules shall show connected loads, total
connected loads per phase.
-
NEC
210-8 shall be amended to apply to all structures.
-
NEC
210-52(b) Exp. 2 shall read as: The receptacle outlet for
refrigeration equipment shall be supplied from an individual branch
circuit rated 15 amperes or greater.
-
At
Article 210-8(b), add new item #3 as follows: OUTDOORS.
-
Sizing
of electrical services for dwellings: (All measurements shall be taken
from the outside of the walls of the dwelling unit).
2500
sq.ft to 3500 sq.ft. shall have a minimum size electrical service of 200
amperes or greater.
Dwelling
units over 3500 sq.ft. shall have electrical services rated at least 350
amperes or greater.
EXCEPTION:
Load calculations may be presented to the Will County Building
Department for review. The Authority Having Jurisdiction determines the
proper size electrical service based on the load calculation submitted.
At no time shall the total calculated load exceed 80% of the service
size.
-
Storage
spaces of 5sq. ft. or more shall be illuminated.
-
All
attic fixtures shall be installed before the rough inspection.
-
All
fixtures shall have at least one lamp installed and all receptacles
intended to be used for switched lighting shall be marked for the
final inspection.
-
All
garages attached or unattached with power are required to be on its
own 20 ampere circuit. (The 20 ampere circuit is a minimum
requirement, more circuits may be added or required as needed.)
-
All
½ horsepower or larger motors and all appliances rated at 1127VA or
greater shall be on its own dedicated circuit.
-
Every
panel box must have each circuit labeled. All electrical panels must
be located a minimum of three (3) feet from sump or ejector pit.
-
At
Article 210-5 add a new subsection as follows, to read:
All
three phase 120/240 volt services shall have phases marked (A) Black (B)
Red and (C) Blue
Add
new subsection (d) as follows:
All
three phase 277/480 volt services shall have phases marked (A) Brown,
(B) Orange (C) Yellow with the neutral being of a gray color. Junction
boxes shall be marked 277/480 volts with a permanent marker or approved
sticker type products.
-
In
commercial and industrial installations all switches for Fire alarms,
Burglar Alarm, shall be equipped with mechanical lockouts to prevent
an accidental turnoff of the circuits.
-
Add
in section 680 Overhead Conductor: No above or inground swimming pool,
hot tub, or recreational equipment capable of holding water or decks
shall be allowed under any aerial wiring . Delete in section 680:
community antenna systems
-
All
commercial/industrial parking facilities having moderate to heavy
traffic shall require Galvanized Steel Conduit (IMC) under the paved
areas for all power and lighting installations.
-
NEC
1999 Article 250-50a1 shall read: Continuity- continuity of the
grounding path or bonding connection to interior piping shall not rely
on water meters, water softeners, water heaters, water filtering
devices or other similar equipment.
|